JV-N
RATING
1. Coil data
Nominal operating
current
[ 10%] (at 20°C 68°F)
Nominal coil
voltage
Pick-up voltage
(at 20°C 68°F)
Drop-out voltage
(at 20°C 68°F)
Coil resistance
[ 10%] (at 20°C 68°F)
Nominal operating
power
Max. applied voltage
(at 20°C 68°F)
4.5V DC
6V DC
44.4mA
33.3mA
22.2mA
16.7mA
11.1mA
8.3mA
101Ω
180Ω
405Ω
9V DC
75%V or less of
nominal voltage
5%V or more of
nominal voltage
150%V of
nominal voltage
12V DC
18V DC
24V DC
48V DC
100V DC
720Ω
200mW
600mW
1,620Ω
2,880Ω
11,520Ω
16,600Ω
4.2mA
Max. 60 VDC
Min. 4 VDC
6
mA
110%V
2. Specifications
Characteristics
Item
Specifications
Arrangement
Contact resistance (Initial)
Contact material
1 Form A
Contact
Max. 100 mΩ (By voltage drop 6 V DC 1A)
AgSnO2 type
Nominal switching capacity (resistive load)
Max. switching power (resistive load)
Max. switching voltage
16A 125V AC, 10A 277V AC, 10A 30V DC
2,770VA, 300W
277V AC, 110V DC (0.3A)
16A (125V AC), 10A (DC)
200mW (4.5 to 48V DC), 600mW (100V DC)
100mA, 5V DC
Rating
Max. switching current
Nominal operating power
Min. switching capacity (reference value)*1
Insulation resistance (Initial)
Min. 1,000MΩ (at 500V DC) Measurement at same location as “Breakdown voltage” section.
1,000 Vrms for 1 min. (Detection current: 10 mA)
Between open contacts
Between contact and coil
Breakdown voltage
(Initial)
2,500 Vrms for 1 min. (Detection current: 10 mA)
Surge breakdown voltage*2
(Between contact and coil) (Initial)
Electrical
characteristics
4,500 V
Operate time (at nominal voltage) (at 20°C 68°F)
(Initial)
Max. 12 ms (4.5 to 48V DC), Max. 8 ms (100V DC) (excluding contact bounce time.)
Release time (at nominal voltage) (at 20°C 68°F)
(Initial)
Max. 5 ms (excluding contact bounce time) (Without diode)
Functional
Shock resistance
200 m/s2 (Half-wave pulse of sine wave: 11 ms; detection time: 10μs.)
1,000 m/s2 (Half-wave pulse of sine wave: 6 ms.)
10 to 55 Hz at double amplitude of 1.6 mm (Detection time: 10μs.)
10 to 55 Hz at double amplitude of 2.0 mm
Destructive
Mechanical
characteristics
Functional
Vibration resistance
Destructive
Mechanical (at 180 times/min.)
Min. 2×107
Min. 3×104 (16A 125V AC), Min. 5×104 (10A 277V AC),
Expected life
Electrical (at 20 times/min.)
Min. 105 (10A 30V DC), Min. 105 (10A 125V AC)
Ambient temperature: –40°C to +70°C –40°F to +158°F (4.5 to 48V DC),
–40°C to +60°C –40°F to +140°F (100V DC),
Conditions for operation, transport and storage*3
Max. operating speed
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature),
Air pressure: 86 to 106kPa
Conditions
Unit weight
20 times/min. (at nominal switching capacity)
Approx. 8 g .28 oz
* Specifications will vary with foreign standards certification ratings.
Notes: *1. This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. Wave is standard shock voltage of 1.2×50μs according to JEC-212-1981
*3. The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
REFERENCE DATA
1. Max. switching power
2. Coil temperature rise
3. Operate/release time
Sample: JVN1aF-12 V-F, 6 pcs.
point measured: coil inside
Contact current: 16 A
Sample: JVN1aF-12 V-F, 6 pcs.
10
100
9
8
7
50
AC resistive load
16
10
Ambient temperature 30°C
40
operate time
6
30
5
4
3
Max.
–
x
Ambient temperature 70°C
1
20
10
0
Min.
release time
2
Max.
–
x
Min.
1
0
80
100
120
140
160
80
100
120 140 160
10
100
1,000
Coil applied voltage, %V
Contact voltage, V
Coil applied voltage, %V
ASCTB189E 201606-T
–2–