MODEL: KYV
H: 220 V AC
J: 240 V AC
Plug-in Signal Conditioners K-UNIT
ISOLATOR
Functions & Features
[4] OPTIONS
blank: none
• Standard instrumentation signal isolator
• Isolation up to 2000 V AC
• High-density mounting
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Typical Applications
• Isolation between control room and field instrumentation
/C02: Polyurethane coating
50
(1.97)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
80
(3.15)
GENERAL SPECIFICATIONS
Construction: Plug-in
123
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
(4.84)
mm (inch)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
MODEL: KYV–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: KYV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. KYV-6A-B/Q)
INPUT SPECIFICATIONS
■ DC Current:
• Specify the specification for option code /Q
(e.g. /C01/S01)
Shunt resistor attached to the input terminals (0.5 W)
[1] INPUT
INSTALLATION
Current
Power input
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
• AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
[2] OUTPUT
Current
Weight: 400 g (0.88 lb)
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
Voltage
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
6: 1 – 5 V DC (Load resistance 500 Ω min.)
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
[3] POWER INPUT
AC Power
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
KYV SPECIFICATIONS
ES-3512 Rev.6 Page 1/2
http://www.m-system.co.jp/