POWR-GARD® Fuse Datasheet
SLC CLASS G FUSES
480/600 VAC • Time-Delay • 1/2-60 A
QPL
Specifications
Voltage Ratings
1
2
600 VAC ( / – 20 A)
480 VAC (25 – 60 A)
1
2
170 VDC ( / – 60 A) (Littelfuse self-certified)
Interrupting Ratings
AC: 100 kA rms symmetrical
DC: 10 kA
1
2
Ampere Range
Approvals
/ – 60 A
Standard 248-5, Class G
UL Listed (File: E81895)
CSA Certified (File: LR29862)
Federal Specification WF-1814
(QPL-W-F-1814)
Environmental
RoHS Compliant
Ordering Information
Description
Littelfuse SLC fuses provide cost effective branch circuit
protection. Fuse length varies to prevent over/fusing.
Compact Class G fuses were the first fuse series to
approach midget fuse dimensions and meet NEC®
requirements for branch/circuit protection.
Part Numbering System
0SLC xxxx T
Series
Package Quantity
T = ꢀ0
Amp Code
Features/Benefits
• Branch circuit rated
• Current/limiting
• ꢀ00 kA interrupting rating
PACKAGE
CATALOG
NUMBER
ORDERING
NUMBER
ꢀ
• 600 VAC rated ꢁ
2
/20 A
SERIES AMP
SLC
QUANTITY
2
10
SLC002
0SLC002.T
Applications
• Branch circuit protection
Dimensions
Ferrule Version
Web Resources
DownloadTC Curves, CAD drawings and other technical
information: littelfuse.com/slc
A
D
C
Recommended Fuse Holders
LFG60 Series (1/20 A)
LFG48 Series (25/60 A)
B
DIMENSIONS INCHES (mm )
AMP
A
B
C
D
1
5
3
3
3
3
9
9
9
13
13
13
13
2
16
8
32
32
/
32
/
32
/
32
/
/ – 15
1 / (33.3)
/ (9.5)
/
/
/
(7.1)
(7.1)
(7.1)
(10.3)
(10.3)
(10.3)
(10.3)
13
32
/
8
32
32
20
1
(35.7)
/ (9.5)
5
8
8
25, 30
35 – 60
1 / (41.3)
/ (9.5)
1
1
4
8
2
2 / (57.2)
/ (9.5)
/ (12.7)
© 2017 Littelfuse POWR-GARD® Products
Rev: 2-B-040417
1 of 1
littelfuse.com