WSYN-50-120-12DC-A

型号:

WSYN-50-120-12DC-A

描述:

并联继电器[ Paralleling Relays ]

品牌:

MACOM[ Tyco Electronics ]

页数:

1 页

PDF大小:

68 K

Paralleling Relays  
Function:  
ANSI/IEEE C37.90-1978  
UL file No. E58048  
25  
WILMARProtective Relays WSYN Series  
TERMINAL STRIPS  
#6 - 32 SCREWS  
CSA file No. LR61158  
Operation:  
A. The output relay will energize when all three  
of the following conditions are met:  
1. Voltage differential is below the preset  
value.  
2. Phase angle is below the preset value.  
3. Frequency differential is below the preset  
value.  
3 1/  
2
B. The relay is also provided with a "Double Dead  
Bus" feature: When the voltage on either one  
of the sensing inputs is below 15-25% of  
nominal, (Dead Bus Condition), the output  
relay will energize to permit paralleling.  
When both sensing voltage are below 15-25%  
of nominal, the output relay will not energize.  
13  
/64  
" DIA.  
4 MTG. HOLES  
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.  
PART NUMBER SELECTION  
Sample Part No.  
WSYN-50-120-12DC-A  
Type:  
WSYN - Synchro Check  
Frequency Hz  
50  
60  
PRODUCT SPECIFICATIONS  
400  
Part Number  
WSYN Series  
Sensing Voltage VAC ( ±10%)  
Sensing Voltage ...................................  
Single Phase, see Part Number Selection  
120  
200  
208  
220  
230  
240  
380  
400  
416  
440  
460  
480  
525  
575  
Control Voltage ....................................  
Voltage Differential Adjust Range .......  
See Part Number Selection  
4% to 10% of nominal voltage  
Phase Angle Adjust Range ..................  
Frequency Differential Adjust Range  
Operating Temperature ........................  
Contact Ratings ....................................  
Output Contacts ...................................  
Notes:  
1. Remove black cover screws to gain access to the adjustment potentiometers.  
2. Clockwise rotation increases the trip differential setting.  
3. Calibration terminals (11) (12) must be connected together to disable the phase angle  
detector when setting the frequency difference trip point. Once it is set, the connection must  
be removed.  
4 to 10 electrical degrees  
0.2 Hz to 0.5 Hz  
Control Voltage ( ±20%)  
-20o C to +50 oC  
12DC  
24DC  
120AC  
230AC  
380AC  
460AC  
5 amp resistive at 120 VAC or 28Vdc  
One set N.O., one set N.C.  
48DC  
125DC  
Options  
A = two normal open contacts  
B = two normally closed contacts  
H = Contacts rated 3 amp at 125 VDC  
P = Transient Protection  
Transient Protection - All voltage relays will withstand  
momentary voltage surges of twice the nominal rated input  
voltage (standard).  
3 8  
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)  
厂商 型号 描述 页数 下载

TE

WSYN 并联继电器[ Paralleling Relays ] 1 页

PDF索引:

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

0

1

2

3

4

5

6

7

8

9

IC型号索引:

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

0

1

2

3

4

5

6

7

8

9

Copyright 2024 gkzhan.com Al Rights Reserved 京ICP备06008810号-21 京

0.199308s